LiteMinder
Peace of Mind never looked so good!
The Lite-Minder Central Inverter System is a sophisticated, versatile, and cost-effective unit that exceeds the features of any comparable system currently available on the market. It has been designed to give users unparalleled ease-of-use, with powerful functionality previously reserved for much larger systems.
The included UL-924 approved Self-Test/Self-Diagnostics features a scrolling LCD display that provides eight points of critical system status events.
DOWNLOADS
Specification Sheets
Installation Instructions
Brochure/Warranty/Typical Wiring
Revit
SPECIFICATION INFORMATION
- Advanced startup diagnostics which protects the unit at initial startup by performing several checks for common installation errors
- Pure Sine Wave output-LED compatible and for all lighting loads
- Fast Transfer System
- An interactive LCD display for easy access to information
- Programmable settings allowing you to personalize to your needs
- Very high, 4x overload rating ensures that even the most demanding loads will start up
- Three distinct output types for field flexibility
- Self-Diagnostics that retain critical data logs, saving you time and money
- Audible diagnostic alarm
- Small foot print fits easily in electrical room or closet, or can be mounted to the wall
- Plenum rated
- No factory startup required
- Tested and Listed by U.L. to UL924 and Canadian Standard
- C 22.2 No. 141-10
- 10 year Lead Calcium or optional 20 year Pure Lead Batteries
- New York City approved, Calendar Number 51575
- Voltage: 120 or 277 VAC Model dependant
- Current: 4.2A (120V), 1.8A (277V) for 325/375 Watt Model
- Frequency: 60Hz +/- 2 Hz
- Protection:Input circuit breaker with KLK fuse in series for easy selective coordination with upstream feed breaker
- Power Factor: 0.5 lead to 0.5 lag
5.8A (120V), 2.5A (277V) for 525/550 Watt Model
- Type: Valve-Regulated sealed Lead Calcium, 10 year design life, Upgrade to Pure Lead with 20 year design life available
- Charger: 3 rate with Temperature Compensation
- Recharge Time: 24 Hour recharge standard
- Runtime: 90 Minutes, initial margin of 125 percent at 25 deg. C, 2 Hour Runtime optional
- Protection: Automatic Low Voltage Disconnect (LVD) set at 1.67 VPC, Automatic Restart Upon Utility Power Return
- DC Voltage: 24 VDC Nominal, 2.27 VPC float, temperature compensated
- DC Current: 24 ADC nominal
- Pure Lead batteries used with 325 VA system are CSA and UL924 listed, when used with 525 VA system are UL924 listed only
- Voltage: 120 or 277 VAC model dependant
- Current: 2.7A (120V), 1.17A (277V) for 325 Watt Model
- 3.13A (120V), 1.36A (277V) for 375 Watt Model
- 4.38A (120V), 1.9A (277V) for 525 Watt Model
- 4.59A (120V), 1.99A (277V) for 550 Watt Model
- Frequency: 60Hz +/- 0.02 Hz crystal controlled during emergency mode
- Overload: 120 percent for 10 minutes, 400 percent for 200 msec
- Transfer Time: <2 msec as standard or can be factory adjusted
- Output Distortion: Less than 3% THD
- Crest Factor: 4 for 525/550 W Model, 6.5 for 325/375 W Model
- Load Power Factor: 0.5 lead to 0.5 lag
- Protection: Optional circuit breakers
- Output Types: Normally On, Normally Off and Switched* (Maintained) Outputs
- Operating Temp: 20 to 30 degrees Centigrade
- Storage Temp: -20 to 70 degrees Centigrade (Electronics) 0-40 degrees Centigrade (Batteries)
- Relative Humidity: <95 % (non-condensing)
- Plenum Rated
- Cooling: Natural Convection – No Fans are required
- Cabinet: NEMA Type 1 enclosure,18 ga. powder painted CRS, 17.8” W x 17.6” H x 12.6” D
- Weight: LM 32 (105 lbs.) LM52 (133 lbs.)
For full warranty details see our warranty data sheet
Electronics:
- Evenlite Inc. warrants the LM series electronics assembly (except batteries) against defects in material and workmanship for a period of three years
Battery:
- Evenlite Inc. warrants the LC series Lead Calcium batteries carry a 1 year full, 9 year pro-rated limited warranty
- The PL series Pure Lead batteries carry a 3 year full, 10 year pro-rated limited warranty.Tested and Listed by U.L. to UL924 and Canadian Standard C 22.2 No. 141-10
- 10 year Lead Calcium or optional 20 year Pure Lead Batteries
- New York City approved, Calendar Number 51575