ELCD 1008
Evenlite’s emergency lighting control device ELCD 1008 is a UL-listed, Branch Circuit Emergency Lighting Transfer Switch (BCELTS) which transfers AC power between two non-synchronous power sources (emergency and normal) to the emergency lighting loads. Coupled with our comprehensive line of emergency lighting inverters, the ELCD 1008 can help turn any lighting fixture into a life-saving emergency egress light source. It is particularly suited for use with line-voltage dimming but can handle all types of lighting loads including 0-10V/DALI dimming with its built-in, auxiliary, low voltage relay, and is fully compliant with the latest 2017 version of the National Electrical Code Article 700. A durable, rugged steel enclosure with a powder-coated finish, coupled with cutting-edge technology and flexible installation features, all combine to make the ELCD 1008 a superior choice above other lighting control devices.
DOWNLOADS
SPECIFICATION INFORMATION
- 16 gauge (0.060”) cold-rolled steel enclosure with textured, powder-coated finish
- 7/8” electrical knock-outs (EKOs) provided on three sides for conduit entry
- Rotatable cabinet with dual-sided, silk-screened panel allows for flexible conduit placement
- PCB-mounted barrier blocks allow for up to 10 AWG wires
- Modular design allows easy removal for field upgrades or servicing
- 120 – 277VAC universal input/output voltage
- 20 amp rating for tungsten, incandescent, ballast/LED driver
- Fire alarm interface with normally-open or normally-closed contact closure • Dimming control interface compatible with 0-10V/DALI
- Latching relay design significantly reduces power consumption
- Short circuit withstand capability of 10kA
- Two internal 30A fuses provide added protection for emergency and normal power circuits
- Size: 9.0”W x 9.5”H x 2.75”D
- Weight: 5.85 lbs.
- Color: Powder painted finish – charcoal gray cabinet (RAL 7016), light gray access plate (RAL 7035)
- Indicator LEDs: Normal power (green), Emergency power (red)
- User controls: Test button, remote laser test
- Mounting: Surface mount (can be plenum mounted)
- Environment: 0-40°C
- UL listed to UL 1008 standard for safety transfer switch equipment BCELTS
- cUL listed to CSA C22.2 emergency transfer switch equipment
- UL listed to UL 2043 for plenum-rated products
- 5-year limited warranty