Tufflite TXPE Class 1 Div 2

Tufflite “TXPE” Industrial Class 1 Division 2 exit signs are designed for use in Class 1 Division 2, Groups A, B, C, D applications.

The rugged fiberglass NEMA 4X enclosure provides protection for the enclosed equipment against dust, dirt, fibers and dripping water. Class 1 locations are those in which flammable vapors and gasses may be present. Division 2 areas are defined as those areas in which ignitable concentrations of hazards are handled, processed or used, but which are normally in closed containers from which they can only escape through accidental rupture or breakdown of such containers or systems. Gases are grouped according to certain physical characteristics of their explosive behavior.

SPECIFICATION INFORMATION

 

  • Designed and listed for use in Class 1 Division 2 Groups A, B, C, and D, T2B area classification, also Suitable for use in Class 1, Zone 2, IIA, IIB, IIC, T1 and T2 area classification
  • Rugged molded corrosion resistant fiberglass enclosure is provided with stainless steel mounting feet, finished in industrial grey
  • A stainless steel breather valve is provided for efficient ventilation of the enclosure
  • Fully gasketed to meet the requirements of NEMA 4X applications
  • Piano hinged front access door for ease of maintenance access with stainless steel screws
  • External 4 hole mounting provision provides ease of installation with minimal cabinet intrusion
  • 6” letter height and 3/4” stroke, with field selectable chevron directional indicators
 

  • High brightness red or green LED’s feature long life and consume less than 2 watts
  • Fully automatic operation provides 90 minutes of emergency operation, with 2 hour run time option available
  • Available as an exit/emergency combination unit, see data sheet TXPC
  • Fully automatic solid state two rate charger provides ideal charge conditions for optimum battery performance and life
  • Field selectable 120 or 277 VAC input
  • Maintenance free Nickel Cadmium batteries recharge in 24 hours following a 90 minute discharge
  • Operating temperature range is 10°C to 45°C
  • Magnetic test switch and dual diagnostic LED indicator displays AC and Hi-Charge status
  • Brownout sensing assures emergency operation during periods of low line voltage
  • Line-latch prevents unnecessary discharge of battery during installation, loads will not illuminate until after application of utility power
  • Low voltage cut-off prevents battery damage and ensures positive charge acceptance following an extended discharge
  • Self-Test / Self-Diagnostic monitoring available
 

  • High capacity models support total loads up to 360 watts or provide for extended discharge period
  • 6 or 12 volt 9 watt tungsten lamps standard
 

  • ARRA compliant for Level 1
  • Listed to UL 924, meets NFPA 101 Life Safety Code, NFPA 70-NEC and OSHA requirements
 

  • 3 year limited warranty