PWII

The Pure Wave II (PWII) was built upon our industry proven PW-Series to engineer a new Dimmable Class of Lighting Inverters with serviceability and flexibility at the forefront of design. Equipped with Pure Sine Wave output, 10X crest factors to punch through the most demanding inrush requirements, 3 configurable lighting zones for seemless system integration, field-selectable Input/Output AC voltages, and ultra-low standby power consumption to meet the California Energy Commission requirements. The PWII offers an industry-leading option of a 3 channel DALI / 0-10V transfer circuit with independent selectable preset dimming levels for each output.

Quick Specs:

  • Input Voltage: 120/277 VAC Field Selectable
  • Max Connected Load:
    • Up to 375W for 120W and 250W Models
    • Up to 1,125W for 375W and 550W Models
  • Output Voltage: 120/277 VAC Field Selectable
  • Output Power:
    • 125W (PWII-12), 250W (PWII-25)
    • 375W (PWII-37), 550W (PWII-55)
  • Load Type: LED, Fluorescent, Incandescent
  • Transfer Time: 50mS / 1S / 2S User Selectable
  • Operating Time: 90 Minutes
  • Overload Capability: Up To 110%
  • Frequency Regulation: 60Hz +/- 0.02 Hz crystal controlled
  • Crest Factor: 10X (125W), 5X (250W), 7.5X (375W), 5X (550W)
  • Load Power Factor: 0.5 lead to 0.5 lag
  • Operating Temperature: 20 — 30 °C
  • Battery Type: Valve Regulated Lead Acid (VRLA)
  • Approval: UL924 Listed

SPECIFICATION INFORMATION

 

  • Field-selectable 120 or 277 VAC Input/Output
  • User adjustable transfer time for application flexibility
  • Optional Dimming Interface (option FD): 3 x DALI / 0-10V w/5 preset levels of 100%, 80%, 60%, 40%, & 20%
  • 1x Normally-On, 3x configurable (Normally-On/Normally-Off or Switched) types for ultimate load flexibility
  • Advanced Startup, Charger, and Inverter Diagnostics for prevention of field failures, overloads and miswires
  • Self-Testing and Self-Diagnostics a standard feature
  • High purity premium maintenance-free Valve Regulated Lead Acid (VRLA) batteries with lead calcium plates for long life and durability
  • T-Bar Mount available in 125 watt model
 

  • Voltage: 120 or 277 VAC – field configurable
  • Current: 2.7A (120V), 1.2A (277V) for 250 Watt Model 1.4A (120V), 0.6A (277V) for 125 Watt Model
  • Frequency: 60Hz +/- 2 Hz
  • Protection: Easy access 8A fast acting 5×20 mm fuse
  • Power Factor: 0.5 lead to 0.5 lag
 

  • Voltage: 120 or 277 VAC (follows Input Voltage selection)
  • Current: 2.08A (120V), 0.9A (277V) for 250 Watt Model 1.04A (120V), 0.45A (277V) for 125 Watt Model
  • Frequency: 60Hz +/- 0.02 Hz crystal controlled (EM mode)
  • Overload Capability: Up to 110%
  • Configurable Transfer Times: 50mS, 1s (default), 2s
  • Output Distortion: Less than 3% THD
  • Crest Factor: 10X for 125W and 5X for 250W model
  • Load Power Factor: 0.5 lead to 0.5 lag
  • Output Types: 1x Normally-On, 3x configurable Normally-Off/Switched
  • Max Connected Load w/ Dimmer option: 375W (Non-EM Mode)
 

  • NEMA Type 1 enclosure, 18 AWG epoxy powder coated Cold Rolled Steel (CRS)
  • Cooling by natural convection – no internal fans
  • Electrical Knock Outs (EKO’s) for ½’ and ¾” conduit provided on three surfaces
 

  • Long-Life Valve-Regulated Lead Acid (VRLA)
  • Ultra efficient 3-rate, temperature-compensation Charger meets CEC Title 20 requirements
  • Automatic Low Voltage Disconnect (LVD) set at 1.67 VPC
  • Runtime: 90 Minutes at 25C°
  • DC Voltage: 24 VDC Nominal, 2.27 VPC float, temperature compensated
  • DC Current: 6.2/12.4 ADC Nominal (125W/250 Watt model)
 

  • Operating Temp: 20C° to 30C°
  • Storage Temp: Electronics – 20C° to 70C° Batteries – 0C° to 40C°
  • Relative Humidity: <95 % (non-condensing)
 

  • UL924
  • NFPA 101 Life Safety Code
  • NFPA 70 – NEC
  • NEMA Type 1 Enclosure
  • NEMA 410 load tested up to 375W